Request A Quote

PG Cable Gland Size Chart: Cable Diameter Guide for PG7–PG48

Author    |    hongxiang_admin    |    October 28, 2026
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
telegram sharing button

Catalogue Sizing Reference

PG Cable Gland Size Chart: Selecting PG7 to PG48 by Cable Diameter

A catalogue-based guide to PG-thread nickel-plated brass cable gland sizing. Match the thread family to the exact cable outer diameter and sealing range.

PG cable gland searches often look simple: a buyer asks for PG7, PG11 or PG16 and expects a single answer. In practice, the PG number identifies the thread family, while the cable outer diameter determines which sealing range is needed. A proper selection must therefore match three details: the finished cable OD, the enclosure’s PG-thread requirement and the exact gland insert range. This guide explains how to use the Hongxiang nickel-plated brass PG catalogue data without treating a thread size as a one-size-fits-all cable solution.

The catalogue’s standard metal PG glands use a nickel-plated brass body, PA66 nylon claw, EPDM or silicone sealing components and EPDM or silicone O-ring. The listed protection level is IP68 at 10 bar, with a normal working temperature of -40°C to 100°C (short-term 120°C). A separate high-temperature metal series covers -40°C to 200°C.

Nickel-plated brass PG cable gland assembled view

1. Why the Same PG Thread Can Have Different Cable Ranges

A PG11 thread does not automatically mean one cable diameter. Hongxiang lists PG11 standard options for 4–8 mm, 5–10 mm and 6–12 mm cables. The installer chooses the version by cable jacket diameter, not merely by the opening in the enclosure. This is especially important for control cable, multicore cable and assemblies where small changes in jacket construction can move the actual OD by several millimetres.

2. Hongxiang PG Cable Gland Size Chart

PG Thread Cable OD Range (listed options) Thread OD
PG7 2–5 mm; 3–6.5 mm; 4–8 mm 12.5 mm
PG9 3–6 mm; 4–8 mm; 5–10 mm 15.2 mm
PG11 4–8 mm; 5–10 mm; 6–12 mm 18.6 mm
PG13.5 5–10 mm; 6–12 mm; 10–14 mm 20.4 mm
PG16 4–8 mm; 6–12 mm; 10–14 mm; 12–16 mm 22.5 mm
PG19 10–14 mm; 12–16 mm 25.0 mm
PG21 4–8 mm; 12–16 mm; 13–18 mm; 15–22 mm 28.3 mm
PG29 15–22 mm; 18–25 mm; 22–30 mm 37.0 mm
PG36 18–25 mm; 22–30 mm; 25–33 mm; 32–38 mm 47.0 mm
PG42 / PG48 30–35 / 32–38 mm; 35–40 / 37–44 mm; 42–52 mm 54.0 / 59.3 mm

Table 1. Hongxiang standard PG nickel-plated brass gland cable OD ranges and thread diameters.

Exploded view of a metal cable gland: lock nut, threaded body, nylon claw, EPDM seal and O-ring

3. Use the Cable OD as Your First Filter

Suppose the cable jacket measures 6.2 mm. The catalogue includes PG7 3–6.5 mm, PG9 3–6 mm, PG11 4–8 mm and other options that may overlap in cable range. The final choice is not determined by OD alone because the enclosure must also accept the required thread. If the panel is already designed for PG7, the PG7 3–6.5 mm option is the relevant starting point.

For a 13–18 mm cable, the standard series lists PG21 13–18 mm, while PG25 includes 15–22 mm and PG29 includes 15–22 mm or 18–25 mm options. The cable diameter and layout may point to different acceptable choices, but the enclosure thread must remain the deciding compatibility check. Never assume that a larger PG thread is automatically a better seal.

4. PG Sizes for Common Industrial Planning

4.1 PG7, PG9 and PG11 for Smaller Cables

These sizes cover small control, signal and instrument cable ranges. PG7 offers options from 2–5 mm through 4–8 mm; PG9 covers 3–6 mm through 5–10 mm; PG11 covers 4–8 mm through 6–12 mm. The overlap is useful for OEM designs, but it makes exact OD measurement essential.

4.2 PG13.5, PG16 and PG21 for Medium Entries

For medium entries, the catalogue shows PG13.5 from 5–10 mm to 10–14 mm, PG16 from 4–8 mm to 12–16 mm, and PG21 from 4–8 mm to 15–22 mm in listed variants. These ranges should be quoted with the exact model code rather than only the thread name.

4.3 PG29 to PG48 for Larger Cables

The larger PG series covers cable ranges from 15–22 mm on selected PG29 models through 42–52 mm on a PG48 option. For large feeders, confirm the equipment opening, spanner clearance, thread length and cable bend arrangement before choosing the gland.

Frequently Asked Questions

Q: What cable size fits a PG7 cable gland?
In the Hongxiang standard PG series, PG7 is listed with 2–5 mm, 3–6.5 mm and 4–8 mm cable ranges. Select the exact option from the measured outer jacket diameter and the relevant product code.
Q: What is the cable range for PG11?
The catalogue lists PG11 variants for 4–8 mm, 5–10 mm and 6–12 mm cable ranges. PG11 alone is not enough information for a purchase order; the required insert range should be stated.
Q: Can I use a PG gland for high-temperature equipment?
Hongxiang lists a dedicated high-temperature metal series with PG7 through PG13.5 options and a stated working temperature of -40°C to 200°C. Check the exact product family and sealing material rather than applying the standard-series rating to high-temperature duty.
Q: Does IP68 depend only on the gland body?
No. The catalogue states IP68 at 10 bar for the listed standard construction, but installation quality, correct cable range, sealing material, thread interface and application conditions also matter. Verify the final assembly requirements for the project.

Standard EPDM seal gland on the right versus silicone seal gland on the left for high-temperature duty

Conclusion: Measure OD, Match the Range, Verify the Thread

PG cable gland selection works best when the thread and cable OD are treated as separate technical checks. Measure the jacket, match it to the exact listed range, verify the enclosure thread, then request the correct model code and drawing. Our technical team provides sizing confirmation, model codes and catalogue data for all PG gland series.

Get the Full PG Size Chart & Model Codes

How Can We Help You?

Our professional team is ready to provide you with prompt and support.

logo

As a trusted cable gland supplier, our connector products serve international markets, including new energy, rail transportation, outdoor lighting, robotics and automation, industrial electrical cable equipment, and computer superservers.

© Copyright 2026 ZHEJIANG HONGXIANG CONNECTOR CO., LTD .

+86-577-62628623